I/O CONTROLLOGIX MESSAGING EXAMPLE
PRODUCT REFERENCE GUIDE
457
Discrete Output Data Object (72 HEX – 1 Instance)
Class Attributes
Attribute ID Name Data Type Data Value Access Rule
1 Revision UINT 1 Get
Instance Attributes
Attribute ID Name Data Type
Default
Data Value
Access Rule
3
Discrete Output
Data
UINT 0 Get / Set
Discrete Output Word
Bit Bit = 0 Bit = 1
0* Trigger Off Trigger On
1 – 7 Unused Unused
8* Reader Relay #1 Off Reader Relay #1 On
9* Reader Relay #2 Off Reader Relay #2 On
10* Reader Relay #3 Off Reader Relay #3 On
11* Reader Relay #4 Off Reader Relay #4 On
12-15 Unused Unused
Common Services
Service Code Implemented for Service Name
Class Level Instance Level
0EHEX Yes Yes
Get_Attribute_Sin-
gle
10HEX No Yes
Set_Attribute_Sin-
gle