Name / value range / [default setting]
(P210.00)
(Min. frequency)
0.0 ... [0.0] ... 599.0 Hz
Lower limit value for all frequency setpoints.
(P211.00)
(Max. frequency)
Device for 50-Hz mains: 0.0 ... [50.0] ... 599.0 Hz
Device for 60-Hz mains: 0.0 ... [60.0] ... 599.0 Hz
Upper limit value for all frequency setpoints.
0x2917
(P220.00)
Acceleration time 1
(Accelerat.time 1)
0.0 ... [5.0] ... 3600.0 s
Acceleration time 1 for the operating mode "MS: Velocity mode".
•
The acceleration time set refers to the acceleration from standstill
to
the maximum frequency set. In the case of a lower setpoint
selection, the actual acceleration time is reduced accordingly.
•
Setting is not effective in the operating mode 0x6060
(P301.00) =
"CiA: Velocity mode [2]".
Device profile CiA 402
299
0x2918
(P221.00)
Deceleration time 1
(Decelerat.time 1)
0.0 ... [5.0] ... 3600.0 s
Deceleration time 1 for the operating mode "MS: Velocity mode".
•
The deceleration time set refers to the deceleration from the
maxi
mum frequency set to standstill. In the case of a lower
actual frequency, the actual deceleration time is reduced
accordingly.
•
Setting is not effective in the operating mode 0x6060
(P301.00) =
"CiA: Velocity mode [2]".
Device profile CiA 402
299
(P225.00)
Quick stop deceleration time
(QSP dec. time)
0.0 ... [1.0] ... 3600.0 s
Quick stop deceleration time for the operating mode "MS: Velocity
mode".
•
If the "Quick stop" function is activated, the motor is brought
to a
standstill within the deceleration time set here.
•
The deceleration time set refers to the deceleration from the
maxi
mum frequency set to standstill. In the case of a lower
actual frequency, the actual deceleration time is reduced
accordingly.
•
Setting is not effective in the operating mode 0x6060
(P301.00) =
"CiA: Velocity mode [2]".
Device profile CiA 402
299
All possible basic settings are described in the "
Basic setting
" chapter.
89