482 01-6203-01R3, CG Drives & Automation
The "Activate fault 2" function was triggered via the NetWordIN1 data word.
The error can only be reset after the function has been deactivated again.
Further process data
191
NetWordIN1 configuration incorrect
Two bits of the NetWordIN1 data word were assigned to the same function.
Remedy: Check and correct the NetWordIN1 data word. The functions that are to be
triggered via bit 0 ... 15 of the NetWordIN1 data word, are defined in
0x400E:001
(P505.01) ... 0x400E:016 (P505.16).
On-board EEPROM: access error
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
25505
0x63A1
CU ID tag error
CU: load error ID tag
Fault
-
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
25507
0x63A3
PU unknown
Power unit unknown
Fault
-
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
On-board EEPROM: timer overflow
Notes:
Logging only (Error history buffer/Logbook)
28800
0x7080
Assertionlevel
Assertion level monitoring (Low/High)
Fault
-
The last setting of the connection level differs from the saved setting.
Remedy:
Check setting in .
Execute device command "Save user data" 0x2022:003 (P700.03).
Switch inverter off and on again.
(P430.10)
The monitoring of the input signal configured for the analog input 1 has been triggered.
Analog input 1
423
28802
0x7082
AI2 fault
Analog input 2 fault
Fault
0x2637:010
(P431.10)
The monitoring of the input signal configured for the analog input 2 has been triggered.
Analog input 2
427
28803
0x7083
HTL input fault
HTL input fault
Warning
-
Error message is not available for the inverter Emotron VS10/30.
Notes:
When the error type is set to "Warning", only logging takes place (Error history buffer/
1
Notes:
Logging only (Error history buffer/Logbook)
2
Error message is not available for the inverter Emotron VS10/30.
Notes:
Logging only (Error history buffer/Logbook)
Pole position identification fault
Serious error: The inverter is inhibited immediately. The motor becomes torqueless