482 01-6203-01R3, CG Drives & Automation
Error code
Info
Error type
Adjustable in
dec
hex
Keypad display
Error message
2
The "Activate fault 2" function was triggered via the NetWordIN1 data word.
The error can only be reset after the function has been deactivated again.
Further process data
191
25265
0x62B1
NetWordIN1 error
NetWordIN1 configuration incorrect
Trouble
-
Two bits of the NetWordIN1 data word were assigned to the same function.
Remedy: Check and correct the NetWordIN1 data word. The functions that are to be
triggered via bit 0 ... 15 of the NetWordIN1 data word, are defined in
0x400E:001
(P505.01) ... 0x400E:016 (P505.16).
25504
0x63A0
EEPROM fault
On-board EEPROM: access error
Fault
-
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
25505
0x63A1
CU ID tag error
CU: load error ID tag
Fault
-
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
25506
0x63A2
PU ID tag error
PU: load error ID tag
Fault
-
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
25507
0x63A3
PU unknown
Power unit unknown
Fault
-
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
25508
0x63A4
EEPROM overflow
On-board EEPROM: timer overflow
Warning
-
Notes:
Logging only (Error history buffer/Logbook)
28800
0x7080
Assertionlevel
Assertion level monitoring (Low/High)
Fault
-
The last setting of the connection level differs from the saved setting.
Remedy:
Check setting in .
Execute device command "Save user data" 0x2022:003 (P700.03).
Switch inverter off and on again.
28801
0x7081
AI1 fault
Analog input 1 fault
Fault
0x2636:010
(P430.10)
The monitoring of the input signal configured for the analog input 1 has been triggered.
Analog input 1
423
28802
0x7082
AI2 fault
Analog input 2 fault
Fault
0x2637:010
(P431.10)
The monitoring of the input signal configured for the analog input 2 has been triggered.
Analog input 2
427
28803
0x7083
HTL input fault
HTL input fault
Warning
-
Error message is not available for the inverter Emotron VS10/30.
Notes:
When the error type is set to "Warning", only logging takes place (Error history buffer/
Logbook)
28833
0x70A
1
AO1 fault
Analog output 1 fault
Warning
-
Notes:
Logging only (Error history buffer/Logbook)
28834
0x70A
2
AO2 fault
Analog output 2 fault
Warning
-
Error message is not available for the inverter Emotron VS10/30.
Notes:
Logging only (Error history buffer/Logbook)
28961
0x7121
Pole pos. error
Pole position identification fault
Fault
0x2C60
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).