Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
Configuration table
TheConfiguration tablehasthefollowingfields:
Power Save:Enableordisablethepowersavefeatureonasystem.
Module Power for Maximum Efficiency: Providesapercentageatwhichthemoduleshouldbe
loadedtoachievemaximumefficiency.Power Save workstogetasclosetothisvalueaspossible.
Refertothemodule’sinstallationmanualtogetinformationforbestperformance.Ifyoudon’thave
thisinformation,usethedefaultvaluebasedontherectifiersused.
Rotate One Module Every:Alengthoftimeindays.Aftertheconfigurednumberofdays,the
modulethathasbeeninstandbylongestwillbeturnedon,themodulethathasbeenonthe
longestwillbeturnedoff.Modulerotationoccursat3am.
Status table
TheStatus tabledisplayswhichvaluesPower Save calculates.Theseincludethefollowingfields:
Power Save:Providesthegeneralstatuswhichmaybeactive,disabled,insufficientredundancy
orinvaliddatasuspended.Power Save cannotoperateifinabatterytest,ifAChasfailedorifany
requireddataisunknown.
Average Power:Providestheaveragemoduleoutputpowercomputedforthesystem.Power
Save willtrytogetthisvalueascloseaspossibletotheModule Power for Maximum Efficiency
(setintheConfiguration table).Forexample:iftheefficiencytargetis80percent,andthe
averagepoweris72percentandturningoffarectifierwouldmaketheaveragepower83percent,
thenPower Save willturnoffarectifiertogetclosertotheefficiencytarget.
# Modules Supplying Power:Thenumberofmodulespresentlysupplyingpower(orcapableof
supplyingpower).Modulesthatarefailed,commslostorhavederatedoutputforanyreasonare
notincludedinthiscount.
#Modules in Standby:Thenumberofmodulespresentlynotsupplyingpowerbutcanbeturned
ontosupplymorepowerasneeded.
Module Rotates In:Provideshowmanyhoursleftuntilthenextmodulerotation(alwaysoccursat
3am).
Estimated Time to Rotate All Modules:Providestheestimatednumberofdaysuntilallmodules
inthesystemwillberotated.Thisvaluechangesdependingonnumberofrectifiersandrotation
period.
Estimated Required Capacity:Providesthecapacityrequiredtosupplytheloadandchargethe
battery.Forexample,ifyourloadis100Aandyourbatterychargecurrentlimitis10A,thisvalue
wouldbe110A.
Estimated Available Capacity:Providestheestimatedavailablecapacityofallmodulesthatare
Supplying Power (modulesIn Standby arenotincluded).
Estimated Redundant Capacity:Providestheestimatedextracapacityofallmodulesthat
aresupplyingpowerinthesystem.InasystemoperatinginFloat mode,somemodulesareIn
Standby, andsomeareSupplying Power. ThemodulesSupplying Power maybeloadedat
0350058-J0 Rev AL Page 77

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish