S7: Memory configuration
14.3 Configuration of the static user memory
Extended Functions
Function Manual, 03/2013, 6FC5397-1BP40-3BA1
761
14.3.2 Commissioning
Procedure
1. Load standard machine data.
2. Preset machine data:
MD18230 $MN_MM_USER_MEM_BUFFERED
with a high value (> default memory available + optional additional memory).
3. Reset the NCK.
Alarm 6030 "User memory limit adjusted" is triggered and the maximum memory
available for the user is entered in MD18230 (including optional memory expansion).
Default values are entered in all other memory-configuration machine data.
4. Set the sizes of partitions U and M in machine data:
MD18352 $MN_MM_U_FILE_MEM_SIZE
(end-user memory for part programs/cycles/files)
MD18353 $MN_MM_M_FILE_MEM_SIZE
(memory size for cycles/files of the machine manufacturer)
5. Activate the number of required channels and axes.
6. You can adjust the default memory division by increasing/decreasing individual memory
areas of the active file system (tool management, global user data, etc.) for each user.
– The static user memory still available is displayed in machine data:
MD18060 $MN_INFO_FREE_MEM_STATIC
(free-static-memory display data)
– Set machine data (see Section "Data lists (Page 764)").
Refere
nces:
Detailed machine-data description
7. Reset the NCK.
The memory is set up again.