H1: Manual and handwheel travel
3.10 Start-up: Handwheels
Extended Functions
206 Function Manual, 03/2013, 6FC5397-1BP40-3BA1
3.10.5 Connected via Ethernet (only 840D sl)
Parameter setting
The parameters for handwheels connected via Ethernet modules, e.g. machine control panel
"MCP 483C IE", "HT 8", or "HT 2", are assigned in the following NC machine data:
● MD11350 $MN_HANDWHEEL_SEGMENT[< x - 1 >] = 7
When connected via Ethernet modules, the segment always has to be entered as 7
(Ethernet).
● MD11351 $MN_HANDWHEEL_MODULE[< x - 1 >] = 1
When connected via Ethernet modules, the module always has to be entered as 1.
● MD11352 $MN_HANDWHEEL_INPUT[< x - 1 >] = y
where y = 1, 2, 3, etc. (handwheel interface at the Ethernet bus)
where x = 1, 2, 3, etc. (handwheel number in the NC)
Handwheel interfaces at the Ethernet Bus
The handwheel interfaces at the Ethernet bus are numbered on the basis of the following
considerations:
● The sequence of the operator component interfaces is: MCP1, MCP2, BHG
● Each operator component interface has two handwheel interfaces
● Operator components: MCP 483C IE
A maximum of two handwheels can be connected to an MCP 483C IE via connections
X60 and X61 . The assignment of the connections in the operator component interface is:
– Connection X60: 1st handwheel in operator component interface MCP1 /MCP2
– Connection X61: 2nd handwheel in operator component interface MCP1 /MCP2
● Operator components: HT 8
The handwheel of the HT 8 is always assigned to the 1st handwheel of operator
component interface MCP1 /MCP2 .
● Operator components: HT 2
The handwheel of the HT 2 is always assigned to the 1st handwheel of operator
component interface BHG .