FuelsManager Defense
120 Administrator Manual
FLOATING
HEIGHT
This field allows the user to configure the height at which the
floating roof is fully floating on the product. FuelsManager
only uses this parameter if the list item ‘Roof Mass not in
Strap’ is selected, otherwise this parameter is ignored
ROOF MASS This field allows the user to configure the weight of the
floating roof. This value is used together with the Roof Type
selection and the current density and strapping density
values to calculate the volumetric effect of the floating roof
ROOF TYPE This field allows the user to configure the type of floating
roof, possible values are:
No Tank Roof - No floating roof correction
Fixed Roof - No floating roof correction
Roof Mass in Strap - Roof mass is accounted for in the tank
strapping table.
Roof Mass not in Strap - Roof mass has not been included in
the tank strapping table
Kaiji-Kentei-Kyyokai - See the Tank Calculations chapter for
more details. Only available if a 'Japan' Correction Type is
selected on the Edit Tank Data Volume tab
Sin-Nihon-Kentei-Kyyoukai1 - See the Tank Calculations
chapter for more details Only available if a 'Japan' Correction
Type is selected on the Edit Tank Data Volume tab
Sin-Nihon-Kentei-Kyyoukai2 - See the Tank Calculations
chapter for more details Only available if a 'Japan' Correction
Type is selected on the Edit Tank Data Volume tab
Sin-Nihon-Kentei-Kyyoukai3 - See the Tank Calculations
chapter for more details Only available if a 'Japan' Correction
Type is selected on the Edit Tank Data Volume tab
TANK
GEOMETRY
This field allows the user to configure the shape of the tank.
FuelsManager uses this value to determine how to
interpolate between strapping table points, possible values
are: Vert. Cylinder; Horizontal Cylinder - End Caps;
Horizontal Cylinder - Flat Ends; Standard Sphere; and
Polynomial Sphere. Selecting Polynomial Sphere causes the
strapping table tab of the tank configuration dialog box to
change to 'Polynomial Sphere'
TANK VOLUME This field allows the user to configure the total internal
volume of the spherical tank.
Used in the LPG calculation method
TANK HEIGHT This field allows the user to configure the total height of the
sphere at the point at which the automatic tank gauge is
installed. Used in the LPG calculation method
TANK RADIUS This field allows the user to configure the radius of the
sphere. Used in the LPG calculation method