376 01-6203-01R3, CG Drives & Automation
The "Enable inverter" 0x2631:001 (P400.01) function must be set to TRUE to
start the motor. Either via digital input or by default setting "Constant TRUE
[1]". If the function is set to FALSE, the inverter is disabled. The motor
becomes torqueless (coasts).
In case of an activated keypad or network control, the "Run" 0x2631:002
(P400.02) function must be additionally set to TRUE to start the motor.
Either via digital input or by the "Constant TRUE [1]" setting.
Notes:
• In case of an activated keypad or network control, the following functions are still
active:
• 0x2631:001 (P400.01): Enable inverter
• 0x2631:002 (P400.02): Run
• 0x2631:003 (P400.03): Activate quick stop
• 0x2631:004 (P400.04): Reset fault
• 0x2631:005 (P400.05): Activate DC braking
• 0x2631:010 (P400.10): Jog foward (CW)
• 0x2631:011 (P400.11): Jog reverse (CCW)
• 0x2631:012 (P400.12): Activate keypad control
• 0x2631:037 (P400.37): Activate network control
• In case of an activated network control, the following additional functions are still
active:
• 0x2631:013 (P400.13): Invert rotation
• The functions for setpoint change-over.Setpoint change-over
378
All other functions configurable via 0x2631:xx (P400.xx) are deactivated in case of
keypad or network control.
Diagnostic parameters:
• 0x282A:001 (P126.01): Cause of disable
• 0x282A:002 (P126.02): Cause of quick stop
• •0x282A:003 (P126.03): Cause of stop
• 0x282B:001 (P125.01): Active control source
For description of the basic functions for controlling the motor, see
chapter "Start / stop
motor".