Example for operating mode
• The keypad is set as standard setpoint source.
• Switch S1 starts the motor in forward direction of rotation. Switch S1 in the initial
position
stops the motor again.
• Switch S2 switches the direction of rotation.
• Switch S3 activates analog input 1 as setpoint source.
• Switch S4 activates analog input 2 as setpoint source.
If S3 and S4 are operated at the same time, the analog input 1 is active as
setpoint source since the digital input 3 assigned to this function has a higher
priority than the digital input 4.
Connection plan
function
Potentiometer R1
Frequency setpoint selection via AI1
Potentiometer R2 Frequency setpoint selection via AI2
Switch S1
Run
Switch S2
Invert rotation
Switch S3
Activate AI1 setpoint
Switch S4
Activate AI2 setpoint
Parameter
Name
Setting for this example
0x2631:001 (P400.01)
Enable inverter
Constant TRUE [1]
0x2631:002 (P400.02)
Run
Digital input 1 [11]
0x2631:004 (P400.04)
Reset fault
Not connected [0]
0x2631:013 (P400.13)
Invert rotation
Digital input 2 [12]
0x2631:014 (P400.14)
Activate AI1 setpoint
Digital input 3 [13]
0x2631:015 (P400.15)
Activate AI2 setpoint
Digital input 4 [14]
0x2631:018 (P400.18)
Activate preset (bit 0)
Not connected [0]
0x2824 (P200.00)
Control selection
Flexible I/O configuration [0]
0x2838:003 (P203.03)
Stop method
Standard ramp [1]
0x2860:001 (P201.01)
Frequency control: Default setpoint source
Keypad [1]