Cordex®CXCHPControllerSoftwareManual|21-Maintainingmodules
3. SelecttheFactory Calibration commandtolaunchthewizard.
4. AttheSelect Type of Calibration step,selectSingle-Point Calibration.
5. Withadigitalvoltmeter,measurethevoltageacrosstheinput.
6. AttheSingle-Point Calibration step,enterthereadingonthevoltmeterintotheMeasured Value
field.
7. SelectNext togotoApply Calibration.Thewizarddisplaystheoldslopeandoffsetandthenew
slopeandoffset.Beforeacceptingthesevalues,ensurethattheslopeisverycloseto1.0andthe
offsetisnomorethanafewvoltsfrom0.0.
8. SelectNext tosendthenewoffsettotheADIOmodule.
9. VerifythatthenewlyCalibrated Value matchesthedigitalvoltmeterreading.SelectDone toexit
thewizard.
21.1.3.4. Temperature input calibration
Notice: Calibration is considered an expert user task. Users must be logged in with Administrator
privileges to perform this calibration.
Tocalibrateaninputcorrectly,youneedhardwaretogenerateandmeasuretheinputsignalaccurately.
ThistopiccovershowtodoaSingle-Point Calibration.IfyouneedtodoaSlope/Offset Calibration or
aTwo-Point Calibration,afactorycalibrationdocumentshouldbewrittenshowing,step-by-step,how
boththehardwareandthesoftwareneedtobeusedtoperformanaccuratecalibration.
To perform a single-point calibration on a temperature input:
1. GotoModules,intheCAN Modules tableselectanADIO andselecttheGO TO buttontoview
theTemperature Inputs table.
2. SelecttheGO TO buttonofaTemperature Input toviewitsindividualmenu.
3. SelecttheFactory Calibration buttontolaunchthewizard.
4. AttheSelect Type of Calibration step,selectSingle-Point Calibration.
5. Withadigitalvoltmeter,measurethevoltageacrosstheinput.
6. AttheSingle-Point Calibration step,enterthereadingonthevoltmeterintotheMeasured Value
field.
7. SelectNext togotoApply Calibration.Thewizarddisplaystheoldslopeandoffsetandthenew
slopeandoffset.Beforeacceptingthesevalues,ensurethattheslopeisverycloseto1.0andthe
offsetisnomorethanafewvoltsfrom0.0.
8. SelectNext tosendthenewoffsettotheADIOmodule.
9. VerifythatthenewCalibrated Value matchesthedigitalvoltmeterreading.SelectDone toexitthe
wizard.
0350058-J0 Rev AL Page 227

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish