Power Characteristics
Table 22: Pilot power characteristics
Power
characteristic
Value
Frequency 50–60Hz
AC voltage 100–240V
Maximum
pow
er
consumption for
both nodes
314 VA
Current draw
for both nodes
1.42A, 208V
Maximum heat
dissipation
1102 BTU/hr
AC receptacle
type
IEC 60320 C14 inlet
Table 23: Controller power characteristics
Power
characteristic
Value
Frequency
(nominal)
50–60 Hz (47–63 Hz range)
Voltage
(nominal)
100 to 127/200 to 240 Volts AC
Input current
(maximum) for
both nodes
13.6 A at 100–120 Volts AC (approximately)
8
A at 200–240 Volts AC (approximately)
Maximum
power
consumption for
both nodes
874 VA (power at maximum FS1 Controller conguration)
Maximum heat
dissipation
2830 BTU/hr
AC receptacle
type
IEC 60320 C14 inlet