Table 26: Low voltage three-phase PDU for Oracle Flash Storage Systems
(continued)
Low Voltage 3Ph (3W + ground)
Voltage input 3Ph [(3W+ground)] 208Vac, 50/60 Hz,
maximum. 40A
per phase
Can be connected to Ph-Ph input sources in
the range of 190V – 220V AC (nominal)
Number of input cords and plug type 1x IEC 309, 60A (Hubbell C460P9W or
equivalent)
Number of data center receptacles and
type
1x IEC 309, 60A (Hubbell 460R9S or
equiv
alent)
Maximum input current for each cord 40A
Outlet receptacles (number/type) 42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
Outlet groups for each PDU 6
PDU power cord length 2 meters (6.6 feet)
PDU power cords are 4 meters (13 feet)
long, but sections are connected for internal
routing in the rack.
Table 27: High voltage single phase PDU for Oracle Flash Storage Systems
High Voltage 1Ph (2W + ground)
kVA size 10 kVA
Marketing part number 7104983
Phase 1
Voltage input 2x [2Ph. (2W+ground)] 230Vac, 50 Hz,
maximum. 25A
per phase
Can be connected to Ph-N input sources in
the range of 220V – 240V AC (nominal)
Number of input cords and plug type 2x IEC 309, 32A (Hubbell 332P6S or
equivalent)
Number of data center receptacles and
type
2x IEC 309, 32A (Hubbell 332R6S or
equivalent)
Oracle FS System Hardware Specifications
237