Table 27: High voltage single phase PDU for Oracle Flash Storage Systems
(continued)
High Voltage 1Ph (2W + ground)
Maximum input current for each cord 25A
Outlet receptacles (number/type) 42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
Outlet groups for each PDU 6
PDU power cord length 2 meters (6.6 feet)
PDU pow
er cords are 4 meters (13 feet)
long, but sections are connected for internal
routing in the rack.
Table 28: High voltage three-phase PDU for Oracle Flash Storage Systems
High Voltage 3Ph (5W + ground)
kVA size 15 kVA
Marketing part number 7104980
Phase 3
Voltage input [3Ph. (4W+ground)] 230/400Vac, 50/60 Hz,
maximum. 25A
per phase
Can be connected to Ph-N input sources in
the range of 220V – 240V AC (nominal)
Number of input cords and plug type 1x IEC 309, 32A (Hubbell 532P6S or
equivalent)
Number of data center receptacles and
type
1x IEC 309, 32A (Hubbell 532R6S or
equivalent)
Maximum input current for each cord 25A
Outlet receptacles (number/type) 42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
Oracle FS System Hardware Specifications
238

Table of Contents

Other manuals for Oracle FS1-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle FS1-2 and is the answer not in the manual?

Oracle FS1-2 Specifications

General IconGeneral
BrandOracle
ModelFS1-2
CategoryStorage
LanguageEnglish

Related product manuals