188 01-6203-01R3, CG Drives & Automation
Parameter
Name / value range / [default setting]
Info
35
Stop sequence
(from version 03.00)
Trigger bit = 0↗1 (edge): Stop sequence.
Trigger bit = 1↘0 (edge): No action.
Notes:
If the sequence is stopped, it is jumped to the final segment.
The further execution depends on the selected End of sequence
mode 0x402F (P824.00).
Sequencer
327
36
Abort sequence
(from version 03.00)
Trigger bit = 0↗1 (edge): Abort sequence.
Trigger bit = 1↘0 (edge): No action.
Notes:
This function serves to directly stop the sequence without the final
segment being executed. In this case, the standard setpoint or the
setpoint source selected via setpoint change-over is active again.
Sequencer
327
39
Activate ramp 2
Trigger bit = 1: activate acceleration time 2 and deceleration time 2
manually.
Trigger bit = 0: no action / deactivate function again.
Frequency limits and ramp times
100
40
Load parameter set
Trigger bit = 0-1 edge: parameter change-over to the value set selected
via "Select parameter set (bit 0)" and "Select parameter set (bit 1)".
Trigger bit = 0: no action.
Notes:
The activation method for the "Parameter change-over" function can
be selected in 0x4046 (P755.00).
Parameter change-over
285
41
Select parameter set (bit 0)
Selection bits for the "Parameter change-over" function.
Parameter change-over
285
42
Select parameter set (bit 1)
43
Activate fault 1
Trigger bit = 1: Trigger user-defined error 1.
Trigger bit = 0: no action.
Notes:
After the error is triggered, the motor is brought to a standstill with
the quick stop ramp. The inverter is then disabled.
Associated error code:
25249 | 0x62A1 Network: user fault 1
44
Activate fault 2
Trigger bit = 1: Trigger user-defined error 2.
Trigger bit = 0: no action.
Notes:
After the error is triggered, the motor is brought to a standstill with
the quick stop ramp. The inverter is then disabled.
Associated error code:
25250 | 0x62A2 Network: user fault 2
45
Deactivate PID controlling
Trigger bit = 1: If PID control is activated, ignore PID control and drive the
motor in speed-controlled manner.
Trigger bit = 0: If PID control is activated, drive the motor with PID
control.
Notes:
The PID control can be activated in 0x4020:001 (P600.01).
Configuring the process controller
232
46
Set PID output to 0
Trigger bit = 1: If PID control is activated, I component and the output of
the PID controller are set to 0 and the internal control algorithm is
stopped. The PID control remains active.
Trigger bit = 0: No action / deactivate function again.
Configuring the process controller
232
47
Inhibit PID I-component
Trigger bit = 1: If the PID control is activated, the I component of the PID
controller is set to 0 and the integration process is stopped.
Trigger bit = 0: No action / deactivate function again.
Configuring the process controller