Oval EL4101 - ⑨ Temperature Input Smoothing Factor Setup (SMOOTHING COEF.)

Oval EL4101
206 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E-880TM-3-E  

  
Temperature input smoothing factor setup (SMOOTHING COEF.)
The smoothing factor with respect to the temperature input is set up here.
  In the SYS mode, this item is not shown if the temperature input type is set to “NONE”.
 Smoothing factor K=1
To temp. input submenu screen p. 50
1
Time constants
Time constant is the time required for the indicated reading to reach 63% of the final level;
it reaches 86% after in twice the time duration of time constant and 95% in three times the
time duration of time constant.
Numerical value input setup
For details of numerical value input setup, see (1) Numerical value setup screen
(INPUT) on page 43.
In the SYS mode, this item is not shown if the temperature input type
( temperature input type setup (TYPE) on page 154) is set to “NONE”.
Do not enter a negative value in the integer part of setting, or it will cause
erratic operation.