SINUS PENTA
PROGRAMMING GUIDE
144/486
P175h1 (P175h2, P175h3) Low-Frequency Flux Increment Percentage for Motor 1 (2,3)
P175h2 (Mot2)
Range
0 ÷ 1000 0.0 ÷ 100.0 %
Function
Percentage of the flux increment at low frequency.
Indicates the increment percent
age of the motor flux, in respect of its nominal
value, adopted up to the frequency value displayed in P175i1
. The flux
increment is dropped to 0 linearly with the frequency (flux equal to the nominal
value) at the frequency value displayed in P175j1.
P175i1 (P175i2, P175i3) Minimum Frequency for Motor 1 (2,3) Flux Increment
P175i2 (Mot2)
Range
0 ÷ 1000 0.0 ÷ 100.0 %
Function
Minimum frequency of the interpolation for the flux increment at low frequency.
Indicates the frequency
(as a percentage of the rated frequency
C015/C058/C101)
up to which a flux increment equal to the value set in
parameter P175h1 is adopted. See the description for P175h1.
P175j1 (P175j2, P175j3) Maximum Frequency for Motor 1 (2,3) Flux Increment
P175j2 (Mot2)
Range
0 ÷ 1000 0.0 ÷ 100.0 %
Function
Maximum frequency of the interpolation for the flux increment at low frequency.
Indicates the frequency
(as a percentage of the rated frequency
C015/C058/C101)
from which the nominal value of the flux is adopted. See the
description for P175h1.
P175t1 (P175t2, P175t3) Proportional Gain of Motor 1 (2,3) Current Controller
P175t2 (Mot2)
Range
0 ÷ 32000 0.000 ÷ 3200.0
Proportional gain of the torque and flux current control (d and q axis).