10. PASSWORD AND USER LEVEL MENU
10.1. Overview
The Password and User Level menu allows changing the programming parameters and sets their visibility.
P000 enables parameter modification
P001 sets the user level
P002 allows to change the password set in P000
P003 conditions required to change C parameters
10.2. List of Parameters P000 to P003
Table 19: List of parameters P000 to P003
Parameter FUNCTION User Level
DEFAULT
VALUES
MODBUS
Address
P000
Write enable
BASIC 00001 513
P001
Programming level
BASIC 0:[Basic] 514
P002
Write enable password
ENGINEERING 00001 510
P003
Conditions required to change C
parameters
ADVANCED StandBy+Fluxing 509
P000 Write Enable
Factory setting is P000 = 1 (parameter write is enabled). To access parameter P000 allowing parameter write, access
the Password and User Level Menu from the Parameters Menu.
P000
Range
00000÷32767
00000: [No] ÷32767
Default
00001
00001
Level
BASIC
Address
Cannot be accessed via serial link.
Parameter write via serial link is always enabled.
Function
Set the correct value in P000 to enable parameter write.
The default password for P000 is 00001.
You can enter a custom password in P002.