51.2. List of Parameters R001 to R013
Table 127: List of parameters R001 to R013
Parameter FUNCTION
User
Level
MODBUS
Address
Default
Values
R001
Drive MODBUS Address for Serial Link 0 (D9-pole)
ENGINEERING
588
1
R002
Response Delay for Serial Link 0 (D9-pole)
ENGINEERING
589
5msec
R003
Baud Rate for Serial Link 0 (D9-pole)
ENGINEERING
590
6:38400 bps
R004
Time added to 4bytetime for Serial Link 0 (D9-pole)
ENGINEERING
591
2msec
R005
Watchdog time for Serial Link 0 (D9-pole)
ENGINEERING
592
0.0sec
R006
Parity Bit for Serial Link 0 (D9-pole)
ENGINEERING
593
1:Disabled 2 Stop-bit
R008
Drive MODBUS address for Serial Link 1 (RJ45)
ENGINEERING
595
1
R009
Response Delay for Serial Link 1 (RJ45)
ENGINEERING
596
5 msec
R010
Baud Rate for Serial Link 1 (RJ45)
ENGINEERING
597
6:38400 bps
R011
Time Added to 4bytetime for Serial link 1 (RJ45)
ENGINEERING
598
2msec
R012
Watchdog Time for Serial Link 1 (RJ45)
ENGINEERING
599
0.0sec
R013
Parity Bit for Serial Link 1 (RJ45)
ENGINEERING
600
1:Disabled 2 Stop-bit
R001 Drive MODBUS Address for Serial Link 0 (D9-pole)
R001
Range
1 ÷ 247
1 ÷ 247
Default
1
1
Level
ENGINEERING
Address
588
Function
This parameter determines the address assigned to the drive connected through
RS485 of serial link 0 (9-pole, male D connector).
R002 Response Delay for Serial Link 0 (D9-pole)
.R002
Range
1 ÷ 1000
1 ÷ 1000 msec
Default
5
5 msec
Level
ENGINEERING
Address
589
Function
This parameter determines the drive response delay after a master query sent
through serial link 0 (9-pole, male D connector).
R003 Baud Rate for Serial Link 0 (D9-pole)
R003 Range
1 ÷ 7
1: 1200 bps
2: 2400 bps
3: 4800 bps
4: 9600 bps
5: 19200 bps
6: 38400 bps
7: 57600 bps
Default
6
6: 38400bps
Level
ENGINEERING
Address
590
Function
This parameter determines the baud rate, expressed in bits per second, for serial
link 0 (9-pole, male D connector).