C172 KEYPAD LOCK Input
C172 Range
0 ÷ 16
0 ÷ 24 if ES847 or ES870 is fitted
0 Inactive
1 ÷ 8 MDI1 ÷ MDI8
9 ÷ 12 MPL1 ÷ MPL4
13 ÷ 16 TFL1 ÷ TFL4
17 ÷ 24 XMDI1 ÷ XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1172
Function
This function avoids accessing parameter modification through the removable
display/keypad and avoids accessing the LOCAL mode by pressing the LOC/REM
key
or by enabling the LOCAL input function (C181).
NOTE
If the LOCAL mode is already active, the LOCK command will have no effect on the
LOCAL function: it only avoids changing
the programming parameters, while it is still
possible to send references and the START/STOP/REV/JOG/RESET commands via
keypad.
If the LOCK command is active and the LOCAL mode is disabled, the LOCK function
prevents the LOCAL mode from activating.
C173, C174 MOTOR SEL Input
C173
C174
Range
0 ÷ 16
0 ÷ 24 if ES847 or ES870 is fitted
0 Inactive
1 ÷ 8 MDI1 ÷ MDI8
9 ÷ 12 MPL1 ÷ MPL4
13 ÷ 16 TFL1 ÷ TFL4
17 ÷ 24 XMDI1 ÷ XMDI8
Default
0
Inactive
Level
ENGINEERING
Address
1173, 1174
Function
This function activates motor 2 and 3 and sets the relevant programming parameters
(see Table 104).
A different active motor can be selected only when the drive is disabled.
Table 104: Motor selection
Value of the terminal allocated to the Sel. Motor
n.2 (C173) function
Value of the terminal allocated to the Sel.
Motor n.3 (C174) function
Active motor
0
0
Motor n.1
1
0
Motor n.2
0
1
Motor n.3
1
1
Motor n.1
NOTE When both inputs are enabled, Motor 1 is selected again.