PROGRAMMING GUIDE
SINUS PENTA
333/486
NOTE
Parameters C154 and C154a may have binary values only and share the same Modbus
address. The bit-parameter matching is given in the table below.
It is important to consider this if the address is updated via an external interface system.
In order
not to change the value of a different parameter, read the address value from the
interface system before operating and make sure that only the bit concerned is modified.
Changes made from the keypad or the RemoteDrive in parameters C154 and C154a are
managed as if the two parameters were completely separate.
Table 99: Address 1154 bits
bit [15..2] bit [1] bit [0]
not used
C154a C154