SINUS PENTA
PROGRAMMING GUIDE
202/486
Example 6: Digital output indicating the READY state to a PLC supervisor using Inputs A, B, C
This example shows how to activate a digital output based on the logic AND of 3 conditions A,B,C—particularly the
ENABLE input, the condition of constant speed reference achieved, and the “Inverter Ok On” condition.
An additional block applied to f(A,B) and C is used:
Table 55: MDO parameterization for the Ready state of a PLC supervisor
P270
MDO1: Digital output mode
DOUBLE DIGITAL
P271
MDO1: Variable A selection
D21: Enable
P272
MDO1: Variable B selection
D40: Speed OK
P273
MDO1: Testing variable A
P274
MDO1: Testing variable B
P275
MDO1: Comparing value for Test A
P276
MDO1: Comparing value for Test B
P277
MDO1: Function applied to the result of the two tests
(A) AND (B)
P277a
MDO1: Variable C selection
D2: Inverter Ok On
P277b
MDO1: Function applied to the result of f(A,B) and C
test
f(A,B) AND (C)
P278
MDO1: Output logic level
TRUE