41.2. List of Parameters C225 to C235
Table 115: List of parameters C225 to C235
Parameter FUNCTION
Procedure in case of Power Down
Stop ramp time in Power Down
Start increment of ramp gradient in P.D.
Improved sensitivity of DC bus control
C230 Voltage level of DC bus in Power Down ENGINEERING 1230
679V for class
4T(380;480V)
707V for class
4T(481;500V)
813V for class 5T
C231
PI Proportional constant for automatic
deceleration
ENGINEERING 1231 0.050
PI Integral time for automatic deceleration
Ramp action at the end of Power Down
Motor speed at the end of Power Down
C225 Procedure in Case of Power Down
C225 Range
0 ÷ 3
0: Disabled
1: Yes
2: YesV
3: Alarm
Function
0: Disabled The Power Down function is disabled.
1: Yes In case of mains loss after a ti
me longer than the time set in
C226 starting from the mains loss detection, the deceleration ramp set in C227
performed.
2: YesV
In case of mains loss, deceleration is automatically regulated by
a PI regulator (see C231 and C232), so that vo
ltage level in DC link is kept
constant at the reference value set in C230.
IFD control: because no torque demand regulation is available, the deceleration
ramp gradient is adjusted depending on the gradient value set in C227.
3: Alarm In case of power failure, the A064 Mains Loss alarm trips
after
the time set in C226.
NOTE
If a drive is DC-powered by a Regenerative Penta (or an equivalent drive
bus voltage), Power Down cannot occur (C008 = xT Regen, where x can be 2, 4, 5, or 6 ).