PROGRAMMING GUIDE
SINUS PENTA
221/486
28. MEASURE CONTROL FROM PT100
28.1. Overview
This menu relates to ES847 control board. It can be viewed only if R023 (I/O board setting) = PT100 (see the
EXPANSION BOARD CONFIGURATION MENU).
The analog inputs can be linked to measure sensors.
NOTE Set DIP-Switches 1 and 2 as follows for proper data acquisition from PT100:
ON
1
SW1
2 3
ON
1
4
5
6 7
ON
1
8
ON
1
SW1
2 3
ON
1
4
5
6 7
ON
1
8
ON
1
2 3
ON
1
4
5
6
7
ON
1
8
ON
1
2 3
ON
1
4
5
6
7
ON
1
8
SW2
28.2. List of Parameters P318 to P325
Table 58: List of parameters P318 to P325
Parameter FUNCTION User Level
DEFAULT
VALUES
MODBUS Address
P320
Channel 1: measure mode
ADVANCED
0: no input
920
P321
Channel 1: measure offset
ADVANCED
0.0 °C
921
P322
Channel 2: measure mode
ADVANCED
0: no input
922
P323
Channel 2: measure offset
ADVANCED
0.0 °C
923
P324
Channel 3: measure mode
ADVANCED
0: no input
924
P325
Channel 3: mesaure offset
ADVANCED
0.0 °C
925
P326
Channel 4: measure mode
ADVANCED
0: no input
926
P327
Channel 4: mesaure offset
ADVANCED
0.0 °C
927