PROGRAMMING GUIDE
SINUS PENTA
315/486
36.3. List of Parameters C140 to C148
Table 94: List of parameters C140 to C148
Parameter FUNCTION User Level
C148
Switch over from
Remote to Local command
ENGINEERING 1148 0: StandBy or Fluxing
NOTE
The programming range of parameters C140, C141, C142
depends on the setting of
parameter C150 and vice versa (see the detailed description of the parameters above).
C140 (C141, C142) Command Source Selection 1 (2, 3)
C140 (C141, C142) Range
0 ÷ 5
1: Terminal Board,
2: Serial Link,
3: Fieldbus,
4: Terminal Board B,
Default
C140 ÷ C141= 1: Terminal Board
C142 = 0: Disabled
C140 ÷ C141 ADVANCED; C142 ENGINEERING
Selection of the drive command source.
NOTE
Setting one of the three command sources to 5: Keypad and one or more of the other
command sources to different values from 5: Keypad is made possible only if:
1. STOP or STOP B digital inputs are set up (C150 ≠ 0 or C150a ≠ 0) to enable
using the pushbuttons or
2. the source selection function is selected (C179 ≠ 0).
NOTE
If the digital input for source selection or command selection (parameter C179 and
C179a in the Digital Inputs Menu) is set to a value other than 0: Disabled, parameter
C142 (Command Source Selection 3)
is always considered as OR bit by bit to the
selected source. The ENABLE input (MDI2), however, is considered as AND to the
selected source.