29. FIELDBUS PARAMETERS MENU
29.1. Overview
This menu allows selecting the Third measure and the Fourth measure from the Fieldbus.
The list of the selectable measures is the same as the list in the MEASURES MENU.
The First measure and the Second measure are fixed (Output Current and Motor Speed) (see Exchanged P).
29.2. List of Parameters P330 to P331
Table 59: List of parameters P330 to P331
Parameter FUNCTION
User
Level
Default
Values
MODBUS
Address
P330
Third measure from the Fieldbus
ENGINEERING
13:Torque Out %
930
P331
Fourth measure from the Fieldbus
ENGINEERING
23: PID Out%
931
P330 Third Measure from the Fieldbus
P330
Range
0-93
See MEASURES MENU and Table 60
Default
13
M012:[Torque Out %]
Level
ENGINEERING
Address
930
Function
Third measure exchanged via Fieldbus.
P331 Fourth Measure from the Fieldbus
P331
Range
0-93
See MEASURES MENU and Table 60
Default
23
M022:[PID Out %]
Level
ENGINEERING
Address
931
Function
Fourth measure exchanged via Fieldbus.