EasyManua.ls Logo

Santerno Sinus Penta - Parameter Modification

Santerno Sinus Penta
486 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINUS PENTA
PROGRAMMING GUIDE
20/486
1.4. Parameter Modification
Factory setting allows parameter modification. The parameters included in the Parameters Menu (Pxxx parameters) can
be changed at any moment, whereas the parameters included in the Configuration Menu (Cxxx, Rxxx, Ixxx
parameters) can be changed only when the motor is stopped.
For safer operating conditions, the configuration parameters must be changed only when the drive is disabled (the
ENABLE-A and ENABLE-B commands are inactive): to do so, P003 must be set to 0 (stand-by only).
To disable parameter changes, just change P000 (write enable) and save its new setting. P000 and P002 (password)
are both factory-set to 1. If P000=0, an inexpert user cannot change parameter values, but if P000=1, an advanced user
will be able to change the parameter values.
For even safer operating conditions, you can change the password stored in P002; in that case, you must set P000
accordingly.
NOTE Note down and keep at hand the value set in P002.
Press the SAVE/ENTER key for parameter modifications; when a flashing cursor appears, press and to change
the parameter value. Do one of the following to quit the editing mode:
Press ESC with P269b = 0: [No]
the parameter value used by the drive is changed and is maintained until the drive is
shut down, then the value is lost when the drive is powered on again.
Press ESC with P269b =1: [YES]
the previous value is restored.
Press SAVE/ENTER
the parameter value is used by the inverter and stored to non-volatile memory and is not
deleted when the drive is shut down.
Inputs (Ixxx) cannot be saved to non-volatile memory and are automatically set to their default values.
Rxxx parameters become active only when the drive control board has been reset by pressing the RESET key for a few
seconds or by switching off the drive.
1.5. Programming the Root Page
When the drive is turned on, the Root page is displayed as the starting page. The Root page allows you to access the
main menus (Measures, Parameters, Configuration, Product ID) or to shift to the Keypad pages using the MENU key.
Root page
I
N
V
E
R
T
E
R
O
K
+
1
5
0
0
.
0
0
r
p
m
+
0
.
0
0
r
p
m
M
E
A
[
P
A
R
]
C
F
I
D
P
You can customise the root page using parameter P265 (see the DISPLAY/KEYPAD MENU).