PROGRAMMING GUIDE
SINUS PENTA
83/486
P001 User Level
P001 Range 0÷2
1: Advanced
Function
The inverter programming parameters are grouped by access levels based on their
functions (more or less complex functions).
Some menus, or some parts of menus, are not displayed when a given access level
is selected.
When the BASIC access level is selected once the invert
correct, navigation is easier, as only frequently accessed parameters are displayed.
The User Level is stated for each parameter.
P002 Password for Write Enable
Function
Once write is enabled after entering the correct password in P000, you can use
parameter P002 to enter a custom password.
CAUTION
The new password allowing parameter write is the value entered in P002.
Note it down and keep it handy!
P003 Conditions for C Parameter Modifications
0:[Stand-by only] ÷ 1:[StandBy+Fluxing]
Function
Factory setting allows C parameters to be programmed even when the inverter is
enabled. However, the motor must be stopped. If P003=0: [Stand-by only],
parameters can be changed only when the inverter is disabled.
This parameter also affects the behaviour of the digital inputs for LOC/REM
motor selection: whe
n those inputs change, they produce their effect only when C
parameters are allowed to be changed, according to the value in P003.
CAUTION
If P003 = 1:[StandBy+Fluxing] when changing a C
parameter, the drive automatically
disables (stops modulating) and the motor starts idling.
NOTE
If C010 = 0: IFD [Voltage/Frequency], C parameters may be set up when the ENABLE-A
and ENABLE-B inputs are active and the motor is stopped independently of P003.