SINUS PENTA
PROGRAMMING GUIDE
92/486
P269 Disable LOC/REM FWD/REV Keys
P269
Range
0 ÷ 3
0:[No No] - 3:[YES YES]
Default
0
0:[No No]
Level
ENGINEERING
Address
869
Function
This parameter allows disabling the LOC/REM and/or the FWD/REV key.
This is a bit-controlled parameter: bit 0 relates to LOC/REM
, while bit 1 relates to
FWD/REV. Set 0 to select [NO], set 1 to select [Yes].
P269 = 0 both keys are enabled.
P269 = 1 the LOC/REM key is disabled.
P269 = 2 the FWD/REV key is disabled.
P269 = 3 both keys are disabled.
P269b ESC Key to Restore Previous Value
P269b
Range
0 ÷ 1
0:[No] - 1:[YES]
Default
0
0:[No]
Level
ENGINEERING
Address
1051
Function
Effect of pressing the ESC key when changing a parameter after pressing
SAVE/ENTER:
P269b = 0:[No] press ESC
to confirm the parameter value, which is not
stored non-
volatile memory (the previous value will be restored when the drive is
next powered on).
P269b = 1:[YES] press ESC to restore the previous value.
In both cases, press SAVE/ENTER
to confirm the new parameter value and
store it to non-volatile memory (the new value is still effective
when the drive is
next powered on).

Table of Contents