Table 42: Cisco ASR 1000 Series Router DC Power Supply System Input Requirements
AWG # WireCircuit Breaker
Amps
System Input
Rating (Amps)
Cisco ASR 1000
Series Router
DC Power
Supply
MaximumMinimumMaximumMinimum
Always AWG
#6 wire
Always 5040Cisco ASR 1006
810403024Cisco ASR 1004
1012302016Cisco ASR 1002
Always AWG
#6 wire
Always 5040Cisco ASR 1013
1010302014Cisco ASR 1001
For example, the
Cisco ASR 1002
Router DC
power supply,
with 16 Amp
input rating
must use an
AWG #12 gauge
wire for a 20 A
circuit breaker
and an AWG
#10 gauge wire
for a 30 A
circuit breaker.
All Cisco ASR 1000 Series Router AC power supplies require a 20 A circuit breaker.Note
The AC and DC power supplies for the Cisco ASR 1000 Series Routers support different types of power
supply switches.
The following table lists AC and DC power supply system rating requirements for all Cisco ASR 1000 Series
Routers.
Cisco ASR 1000 Series Router Hardware Installation Guide
124
Preparing Your Site for Installation
Site Power Guidelines

Table of Contents

Other manuals for Cisco ASR 1004

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco ASR 1004 and is the answer not in the manual?

Cisco ASR 1004 Specifications

General IconGeneral
BrandCisco
ModelASR 1004
CategoryNetwork Router
LanguageEnglish

Related product manuals