RPDO1 mapping
The RPDO1 is used to control the inverter.
Changing the identifier (COB-ID) and the PDO mapping only allows the following
procedure:
1. Set RPDO1 to "invalid": Set bit 31 in the identifier 0x1400:001 (P540.01) to "1".
2. Set RPDO1 mapping to "invalid": 0x1600:000 = set 0.
3. Map NetWordIN1 data word0x4008:001 (P590.01) to RPDO1: 0x1600:001 = set
0x40080110.
4. MapNetwork setpoint frequency (0.1) 0x400B:003 (P592.03) to RPDO1: 0x1600:002 =
set 0x400B0310.
5. Set RPDO1 mapping to "valid" again: 0x1600:000 = set 2 (number of mapped
parameters).
6. Optional: Set time-out time for monitoring the data reception in 0x1400:005
(P540.05) in [ms].
• Default setting: 100 ms
7. Change identifier for RPDO1 (optional) and set RPDO1 to "valid" again: Write the new
identifier into 0x1400:001 (P540.01) and simultaneously set bit 31 to "0".
• Default setting: 0x200 + node address (hex)
• Example: Node address = 10 (0xA) and basic identifier = default setting:
Identifier to be written into 0x1400:001 (P540.01) = 0x200 + 0xA = 0x20A (0b0011
0000 1010)
Function assignment of the NetWordIN1 data word (byte 1+2 of the RPDO1)
For details and configuration, see
2
Activate quick stop
0x400E:003 (P505.03)
7
Reset error
0x400E:008 (P505.08)
12
Invert rotation
0x400E:013 (P505.13)
Specifying the frequency setpoint (byte 3+4 of the RPDO1)
• The specification is made unsigned (independent of the direction of rotation) as
integer in the resolution [0.1 Hz].
• The direction of rotation is defined in the default setting via bit 12 of the NetWordIN1
data word.
• Example: 456 ≡ 45.6 Hz