Parameter
Name / value range / [default setting]
Info
0x402E:002
(P822.02)
End segment: Acceleration/deceleration
(End segment: Accel./decel.)
0.0 ... [5.0] ... 3600.0 s
From version 03.00
If end of sequence mode = "continuous operation" (default setting):
Acceleration/deceleration for reaching the frequency setpoint set for the
end segment after the sequence has been processed.
If end of sequence mode = "Stop" or "Stop and abort": Deceleration for
reaching standstill after the sequence has been processed.
Only relevant for operating mode 0x6060 (P301.00) = "MS: Velocity
mode [-2]".
The set time refers to the acceleration from standstill to the set
maxi
mum frequency. The deceleration is effected with the same
ramp.
0x402E:003
(P822.03)
End segment: Time
(End segment: Time)
0.0 ... [0.0] ... 100000.0 s
From version 03.00
Delay time for activating the output states configured for the end
segment.
This parameter has a different meaning than the time settings for the
segments 1 ... 8!
The set deceleration time starts when the end segment is started to
be processed.
After the deceleration time has elapsed:
The digital output is set to the level set in 0x402E:004 (P822.04) (if
configured accordingly).
The analog output is set to the voltage value set in 0x402E:005
(P822.05) (if configured accordingly).
The NetWordOUT2 data word is set to the value set in 0x402E:008.
0x402E:004
(P822.04)
End segment: Digital outputs
(End segment: Digital outp.)
0 ... [0] ... 255
From version 03.00
Optionally: Set digital outputs to the levels set here after the time set
for the end segment.
Bit 0
Relay
0 = X9/NO-COM open and NC-COM closed.
1 = X9/NO-COM closed and NC-COM open.
An inversion set in 0x2635:001 (P421.01)is taken into consideration
here.
Bit 1
Digital output 1
0 = set digital output 1 to LOW level.
1 = set digital output 1 to HIGH level.
An inversion set in 0x2635:002 (P421.02) is taken into consideration
here.
Bit 2
Digital output 2
Not available for inverter Emotron VS10/30.
0x402E:005
(P822.05)
End segment: Analog outputs
(End segment: Analog outp.)
0.00 ... [0.00] ... 10.00 VDC
From version 03.00
Optionally: Set analog output to the voltage value set here after the time
set for the end segment.
Note!
In order that the control of the analog output is executed by the
sequencer, the following assignment must be made for the analog
output:
Analog output 1: 0x2639:002 (P440.02) = "Sequencer controlled [10]"
0x402E:006
(P822.06)
End segment: PID setpoint
(End segment: PID setp.)
-300.00 ... [0.00] ... 300.00 PID unit
From version 03.00
PID control value after the sequence has been completed, i. e., after the
steps configured for the sequence have been passed through with the
set numbers of cycles.
Only relevant if PID control is activated in 0x4020:001 (P600.01)
and
end of sequence mode 0x402F (P824.00) = "Keep running [0]".
0x402E:007
(P822.07)
End segment: Torque setpoint
(End segment: Torque setp.)
-400.0 ... [100.0] ... 400.0 %
From version 03.00
Torque setpoint after the sequence has been completed, i. e., after the
steps configured for the sequence have been passed through with the
set numbers of cycles.
Only relevant for the operating mode 0x6060 (P301.00) = "MS: Torque
mode [-1]" and if end of sequence mode 0x402F (P824.00)
= "Keep
running [0]".
0x402E:008
End segment: NetWordOUT2
0 ... [0] ... 65535
From version 03.00
Optionally: Set NetWordOUT2 data word to the value set here after the
time set for the end segment.
The NetWordOUT2 data word 0x400A:002 (P591.02) can be mapped
to
a network register to transfer the set value as process date.
0x402E:009
End segment: Position setpoint
0 ... [0] ... 4294967295