SINUS PENTA
PROGRAMMING GUIDE
102/486
P024 Deceleration Ramp: Start Rounding Off Time
P024
Range
0 ÷ 100
0 ÷ 100 %
Default
See Table 82 and Table 86
Level
ADVANCED
Address
624
Function
See the function for P022
. The only difference is that this rounding off function is
applied to the first stage of a deceleration ramp.
NOTE
When using parameter P024, t
he preset deceleration ramp time is increased by:
(P024%)/2.
P025 Deceleration Ramp: End Rounding Off Time
P025
Range
0 ÷ 100
0 ÷ 100 %
Default
See Table 82 and Table 86
Level
ADVANCED
Address
625
Function
See the function for P023
. The only difference is that this rounding off function is
applied to the last stage of a deceleration ramp.
NOTE
When using parameter P025, the preset deceleration ramp time is inc
reased by:
(P025%)/2.
P026 Torque Ramp Time: Up
P026
Range
0 ÷ 32700
Function of P028
Default
500
50 sec
Level
ADVANCED
Address
626
Function
Defines the time taken by the torque reference of the selected motor to go to zero
from max. value (as a
n absolute value between Torque min. and Torque max.);
(
C047
C048
for motor 1 and so on).
P027 Torque Ramp Time: Down
P027
Range
0 ÷ 32700
Function of P028
Default
500
50 sec
Level
ADVANCED
Address
627
Function
Defines the time taken by the torque reference of the selected motor to go from max.
value to zero (as an absolute value between Torque min. and Torque max.); (C047
C048 for motor 1 and so on).