SINUS PENTA
PROGRAMMING GUIDE
104/486
P032 Fire Mode Acceleration Ramp
P032 Range
0 ÷ 32700
0 ÷ 327.00 s if P014=0 0.01 s
0 ÷ 3270.0 s if P014=1
0.1 s
0 ÷ 32700 s if P014=2
1 s
0
÷
327000 s if P014=3 10 s
Default
See Table 82 and Table 86
Level
ENGINEERING
Address
632
Function This ramp is used to accelerate the motor when in Fire Mode.
P033 Fire Mode Deceleration Ramp
P033 Range
0 ÷ 32700
0 ÷ 327.00 s if P014=0 0.01 s
0 ÷ 3270.0 s if P014=1
0.1 s
0 ÷ 32700 s if P014=2
1 s
0 ÷ 327000 s if P014=3 10 s
Default
See Table 82 and Table 86
Level
ENGINEERING
Address
633
Function
This ramp is used to decelerate the motor when in Fire Mode.