PROGRAMMING GUIDE
SINUS PENTA
281/486
C017 (C060,C103) Rated Motor Power
C060 (Motor 2)
Range
1 ÷ 32000 0.1 ÷ 3200.0 kW
Upper limited to twice the default value
See Table 84 and Table 88
This parameter defines the rated motor power (nameplate rating).
C018 (C061, C104) Rated Motor Current
C018 (Motor 1)
C061 (Motor 2)
Range
1 ÷ 32000 0.1 ÷ 3200.0 A
Upper limited to the values in Inom column in Table 81 and Table 85
See Table 84 and Table 88
This parameter defines the rated motor current (nameplate rating).
C019 (C062, C105) Rated Motor Voltage
C062 (Motor 2)
Range
50 ÷ 12000 5.0 ÷ 1200.0 V
Default
4000 for class 4T drives
5750 for class 5T drives
230.0V for class 2T drives
400.0V for class 4T drives
575.0V for class 5T drives
690.0V for class 6T drives
This parameter defines the rated motor voltage (nameplate rating).
C020 (C063, C106) Motor No-Load Power
C063 (Motor 2)
Range
0 ÷ 1000 0.0 ÷ 100.0%
Function
This parameter defines the power absorbed by the motor at rated voltage and rated
rpm when no load is connected to the motor.
C021 (C064,C107) Motor No-Load Current
C064 (Motor 2)
Range
1 ÷ 100 1 ÷ 100%
Function
This parameter defines the current absorbed by the motor at rated voltage and
rated rpm when no load is connected to the motor. It is expressed as a percentage
of the motor rated current C018 (C061, C104
). For a proper tuning of the current
loops required for FOC control, enter a value other than zero.
If the stator resistance is tuned (I073 = [1: Motor Tune]); 1074 = [0: Motor Params]
and the no load current parameter is zero, a value
for a first attempt is assigned to
this parameter, depending on power and pole pairs of the connected motor.