SINUS PENTA
PROGRAMMING GUIDE
454/486
A039 Texas Flash not Programmed
A039 Description Texas Flash not programmed
Event
When switched on, DSP Motorola detected that Flash Texas is not correctly
programmed.
A prior attempt to download DSP Texas software failed.
Solution
1. Download the correct DSP Texas software version.
2. If the alarm persists, please contact ELETTRONICA SANTERNO’s Customer
A040 User Alarm
A040 Description
Alarm trip caused by the user (as a system testing procedure)
The user has forced the alarm to trip.
Value 1 was entered to address MODBUS 1400 via serial link.
Reset the alarm: send a RESET command.
A041 IGBT Fault Side A
A041 Description
General hardware fault from IGBT, side A
Power converter A generated a general alarm.
• Electromagnetic disturbance or radiated interference.
• Overcurrent, IGBT overtemperature, IGBT fault.
Solution
1. Reset the alarm: send a RESET command.
2. If the alarm persists, please contact ELETTRONICA SANTERNO’s Customer
A042 Illegal XMDI in DGI
A042 Description Illegal configuration of XMDI in the Digital Inputs menu.
Event
• The drive checked if at least one XMDI input from ES847 or ES870 I/O optional
board is available in the DIGITAL INPUTS MENU;
• The drive checked if R023 (I/O Board setting) is set to 0 in the
EXPANSION BOARD
CONFIGURATION MENU
Wrong settings.
Solution
Check settings and enter correct settings.