SINUS PENTA
PROGRAMMING GUIDE
242/486
P366 MPL2: Function Applied to the Result of the 2 Tests
P366 Range
0 ÷ 12
1: (A) SET (B) RESET
2: (A) AND (B)
3: (A) XOR (B)
4: (A) NOR (B)
5: (A) NAND (B)
6: (A\) OR (B)
7: (A) OR (B\)
8: (A\) AND (B)
9: (A) AND (B\)
10: (A) RESET (B) SET RISING EDGE
11: (A) SET (B) RESET FALLING EDGE
12: (A) RESET (B) SET FALLING EDGE
Function
This parameter determines the logic function applied to the result of the two
tests allowing calculating the output value.
P366a MPL2: Selecting Variable C
Function
This parameter selects the digital signal used to calculate the value of MPL2
digital output.
The digital signals that can be selected are given in Table 48.
P366b MPL2: Function Applied to the Result of f(A,B) C
P366b Range
0 ÷ 12
1: f(A,B) SET (C) RESET RISING EDGE
2: f(A,B) AND (C)
3: f(A,B) XOR (C)
4: f(A,B) NOR (C)
5: f(A,B) NAND (C)
6: (A\) OR (B)
7: (A) OR (B\)
8: (A\) AND (B)
9: (A) AND (B\)
10: (A) RESET (B) SET RISING EDGE
11: (A) SET (B) RESET FALLING EDGE
12: (A) RESET (B) SET FALLING EDGE
Function
This parameter determines the logic function applied to the result of the two
tests allowing calculating the output value.