2 Parameters
2.2 List of parameters
SINAMICS G120D
100  List Manual (LH14), 01/2016, A5E33842313
Description: Sets the reference values for the specific scaling of BICO parameters.
The specific scaling is active when interconnecting with other BICO parameters, and can be used in the following 
cases:
1. Parameter with the marking "Scaling: p0514".
2. Changing the standard scaling for parameters with the marking "Scaling: p2000" ... "Scaling: p2007".
Relative values refer to the corresponding reference value. The reference value corresponds to 100% or 4000 hex 
(word) or 4000 0000 hex (double word).
To specifically scale BICO parameters, proceed as follows:
- set the reference value (p0514[0...9]).
- set the numbers of the parameters, which should be active for the scaling, corresponding to the index of p0514 
(p0515[0...19] ... p0524[0...19]).
For parameters with the marking "Scaling: p0514", which are not entered in p0515[0...19] to p0524[0...19], the 
reference value 1.0 (factory setting) applies.
Index: [0] = Parameters in p0515[0...19]
[1] = Parameters in p0516[0...19]
[2] = Parameters in p0517[0...19]
[3] = Parameters in p0518[0...19]
[4] = Parameters in p0519[0...19]
[5] = Parameters in p0520[0...19]
[6] = Parameters in p0521[0...19]
[7] = Parameters in p0522[0...19]
[8] = Parameters in p0523[0...19]
[9] = Parameters in p0524[0...19]
Dependency: Refer to: p0515, p0516, p0517, p0518, p0519, p0520, p0521, p0522, p0523, p0524
Description: Sets the parameters with reference value in p0514[0] for the specific scaling.
p0515[0]: parameter number
p0515[1]: parameter number
p0515[2]: parameter number
...
p0515[19]: parameter number
Dependency: Refer to: p0514
Description: Sets the parameters with reference value in p0514[1] for the specific scaling.
p0514[0...9] Scaling-specific reference values / Scal spec ref val
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting 
0.000001 10000000.000000 1.000000 
p0515[0...19] Scaling specific parameters referred to p0514[0] / Scal spec p514[0]
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting 
0 4294967295 0 
p0516[0...19] Scaling specific parameters referred to p0514[1] / Scal spec p514[1]
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting 
0 4294967295 0