2 Parameters
2.2 List of parameters
SINAMICS G120D
52 List Manual (LH14), 01/2016, A5E33842313
Note: When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application (p0500)
and the control mode (p1300) are pre-assigned according to the selected application. The parameter has no
influence when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
Description: Displays the rated power unit power for various load duty cycles.
Index: [0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Dependency: IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100, p0205
Description: Displays the rated power unit power for various load duty cycles.
Index: [0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Dependency: Refer to: p0205
Description: Displays the rated line supply voltage of the power unit.
r0208 = 400: 380 - 480 V +/-10 %
r0208 = 500: 500 - 600 V +/-10 %
r0208 = 690: 660 - 690 V +/-10 %
Description: Displays the maximum output current of the power unit.
r0206[0...4] Rated power unit power / PU P_rated
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: 14_6 Unit selection: p0100 Func. diagram: -
Min Max Factory setting
- [kW] - [kW] - [kW]
r0207[0...4] Rated power unit current / PU PI_rated
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8021
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0208 Rated power unit line supply voltage / PU U_rated
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r0209[0...4] Power unit maximum current / PU I_max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8750, 8850, 8950
Min Max Factory setting
- [Arms] - [Arms] - [Arms]