Siemens SINAMICS G120D CU240D-2 DP - r5398[0...n] Mot_temp_mod 3 alarm threshold image p5390; A thr image p5390; r5399[0...n] Mot_temp_mod 3 fault threshold image p5391; F thr image p5391; r5600 Pe energy-saving mode ID; Pe mode ID; p5602[0...1] Pe energy-saving mode pause time minimal; Pe mod t_pause min

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
415
2 Parameters
2.2 List of parameters
Description: Displays the alarm threshold for monitoring the motor temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p5390.
Dependency: Refer to: p5390
Refer to: F07011, A07012, A07014
Note: Users cannot see and change parameter p5390 (only Siemens internal).
Description: Sets the fault threshold for monitoring the motor temperature for motor temperature model 3.
Fault F07011 is output after the fault threshold is exceeded.
The parameter value is an image of p5391.
Dependency: Refer to: p5391
Refer to: F07011, A07012, A07014
Note: Users cannot see and change parameter p5391 (only Siemens internal).
Description: Displays the PROFIenergy mode ID of the effective energy-saving mode.
Value: 0: POWER OFF
1: Energy-saving mode 1
240: Operation
255: Ready
Note: Pe: PROFIenergy profiles
Description: Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time regular
- Energy-saving mode, time of minimum stay
Index: [0] = Mode 1
[1] = Reserved
r5398[0...n] Mot_temp_mod 3 alarm threshold image p5390 / A thr image p5390
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8019
Min Max Factory setting
- [°C] - [°C] - [°C]
r5399[0...n] Mot_temp_mod 3 fault threshold image p5391 / F thr image p5391
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8019
Min Max Factory setting
- [°C] - [°C] - [°C]
r5600 Pe energy-saving mode ID / Pe mode ID
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2381, 2382
Min Max Factory setting
0 255 -
p5602[0...1] Pe energy-saving mode pause time minimal / Pe mod t_pause min
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2381
Min Max Factory setting
300000 [ms] 4294967295 [ms] [0] 300000 [ms]
[1] 480000 [ms]