2 Parameters
2.2 List of parameters
SINAMICS G120D
194 List Manual (LH14), 01/2016, A5E33842313
Dependency: Refer to: p1231, p1232, p1233, p1234
Note: For bit 12, 13:
Only effective for p1231 = 14.
Description: Sets the maximum search frequency for a flying restart in an inhibited setpoint direction (p1110, p1111).
Note: The parameter has no effect for an operating mode, which only searches in the setpoint direction (p1200 > 3).
Description: Sets the configuration for the DC link voltage controller.
Note: For bit 00:
De-activate the ramp-up for Vdc_min control.
For drives with a mechanical system that can oscillate and high moment of inertia, the speed can be more quickly
tracked.
For bit 02:
When the line supply returns, normal operation is resumed earlier, and the system does not wait until the Vdc min
controller reaches the setpoint speed.
Description: Sets the open and closed-loop control mode of a drive.
Value: 0: U/f control with linear characteristic
1: U/f control with linear characteristic and FCC
2: U/f control with parabolic characteristic
3: U/f control with parameterizable characteristic
4: U/f control with linear characteristic and ECO
5: U/f control for drives requiring a precise freq. (e.g. textiles)
6: U/f control for drives requiring a precise frequency and FCC
7: U/f control for a parabolic characteristic and ECO
19: U/f control with independent voltage setpoint
20: Speed control (encoderless)
21: Speed control (with encoder)
22: Torque control (encoderless)
23: Torque control (with encoder)
12 DC braking selection internally inhibited Yes No -
13 DC braking for OFF1/OFF3 Yes No -
p1271[0...n] Flying restart maximum frequency for the inhibited direction / FlyRes f_max dir
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [Hz] 650 [Hz] 0 [Hz]
p1281[0...n] Vdc controller configuration / Vdc ctrl config
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Vdc min control (U/f) without up ramp Yes No -
02 Vdc min shorter wait time when the line
returns
Yes No -
p1300[0...n] Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6300, 6301, 8012
Min Max Factory setting
0 23 0