Siemens SINAMICS G120D CU240D-2 DP - p9570 SI Motion acceptance test mode (processor 1); SI Mtn acc_mod P1; r9571 SI Motion acceptance test status (processor 1); SI Mtn acc_status; p9581 SI Motion brake ramp reference value (processor 1); SI Mtn ramp ref P1; p9582 SI Motion brake ramp delay time (processor 1); SI Mtn ramp t P1

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
455
2 Parameters
2.2 List of parameters
Description: Setting to select and de-select the acceptance test mode.
Value: 0: [00 hex] De-select the acceptance test mode
172: [AC hex] Select the acceptance test mode
Dependency: Refer to: p9558, r9571, p9601
Refer to: C01799
Note: Acceptance test mode can only be selected if the motion monitoring functions, which are integrated in the drives, are
enabled (p9601.2/p9801.2).
Description: Displays the status of the acceptance test mode.
Value: 0: [00 hex] Acc_mode inactive
12: [0C hex] Acc_mode not possible due to POWER ON fault
13: [0D hex] Acc_mode not possible due to incorrect ID in p9570
15: [0F hex] Acc_mode not possible due to expired Acc_timer
172: [AC hex] Acc_mode active
Dependency: Refer to: p9558, p9570
Refer to: C01799
Description: Sets the reference value to define the brake ramp.
The rate of rise of the brake ramp depends upon p9581 (reference value) and p9583 (monitoring time).
Dependency: Refer to: p9582, p9583
Description: Sets the delay time for monitoring the brake ramp.
Monitoring of the brake ramp starts once the delay time has elapsed.
Dependency: Refer to: p9581, p9583
Note: The set time is rounded internally to an integer multiple of the monitoring clock cycle.
Internally, the set time is limited downwards to 2 safety monitoring clock cycles (2 * 12 ms).
p9570 SI Motion acceptance test mode (processor 1) / SI Mtn acc_mod P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00AC hex 0000 hex
r9571 SI Motion acceptance test status (processor 1) / SI Mtn acc_status
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00AC hex -
p9581 SI Motion brake ramp reference value (processor 1) / SI Mtn ramp ref P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
600.0000 [rpm] 240000.0000 [rpm] 1500.0000 [rpm]
p9582 SI Motion brake ramp delay time (processor 1) / SI Mtn ramp t P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
10.00 [ms] 99000.00 [ms] 250.00 [ms]