2 Parameters
2.2 List of parameters
SINAMICS G120D
128 List Manual (LH14), 01/2016, A5E33842313
Description: Sets the setpoint for the input signals in the digital input simulation mode.
Dependency: The simulation of a digital input is selected using p0795.
Refer to: p0795
Note: This parameter is not saved when data is backed up (p0971).
DI: Digital Input
Description: Sets the simulation mode for the analog inputs.
Value: 0: Terminal evaluation for analog input x
1: Simulation for analog input x
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency: The setpoint for the input voltage is specified via p0798.
Refer to: p0798
Note: This parameter is not saved when data is backed up (p0971).
AI: Analog Input
Description: Sets the setpoint for the input value in the simulation mode of the analog inputs.
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency: The simulation of an analog input is selected using p0797.
If AI x is parameterized as a voltage input (p0756), the setpoint is a voltage in V.
Refer to: p0756, p0797
Note: This parameter is not saved when data is backed up (p0971).
AI: Analog Input
p0796 CU digital inputs simulation mode setpoint / CU DI simul setp
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2210, 2256
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X07.4) High Low -
01 DI 1 (X07.2) High Low -
02 DI 2 (X08.4) High Low -
03 DI 3 (X08.2) High Low -
04 DI 4 (X09.4) High Low -
05 DI 5 (X09.2) High Low -
p0797[0...1] CU analog inputs simulation mode / CU AI sim_mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p0798[0...1] CU analog inputs simulation mode setpoint / CU AI sim setp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-50.000 2000.000 0.000