Siemens SINAMICS G120D CU240D-2 DP - p2200[0...n] BI: Technology controller enable; Tec_ctrl enable; p2201[0...n] CO: Technology controller fixed value 1; Tec_ctrl fix val1; p2202[0...n] CO: Technology controller fixed value 2; Tec_ctr fix val 2; p2203[0...n] CO: Technology controller fixed value 3; Tec_ctr fix val 3

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
313
2 Parameters
2.2 List of parameters
Description: Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
Description: Sets the value for fixed value 1 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 2 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 3 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 4 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2200[0...n] BI: Technology controller enable / Tec_ctrl enable
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0
p2201[0...n] CO: Technology controller fixed value 1 / Tec_ctrl fix val1
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7950, 7951
Min Max Factory setting
-200.00 [%] 200.00 [%] 10.00 [%]
p2202[0...n] CO: Technology controller fixed value 2 / Tec_ctr fix val 2
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7950, 7951
Min Max Factory setting
-200.00 [%] 200.00 [%] 20.00 [%]
p2203[0...n] CO: Technology controller fixed value 3 / Tec_ctr fix val 3
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7950, 7951
Min Max Factory setting
-200.00 [%] 200.00 [%] 30.00 [%]
p2204[0...n] CO: Technology controller fixed value 4 / Tec_ctr fix val 4
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7950, 7951
Min Max Factory setting
-200.00 [%] 200.00 [%] 40.00 [%]