Siemens SINAMICS G120D CU240D-2 DP - p2187[0...n] Load monitoring torque threshold 2 upper; M_thresh 2 upper; p2188[0...n] Load monitoring torque threshold 2 lower; M_thresh 2 lower; p2189[0...n] Load monitoring torque threshold 3 upper; M_thresh 3 upper; p2190[0...n] Load monitoring torque threshold 3 lower; M_thresh 3 lower

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
309
2 Parameters
2.2 List of parameters
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2189 > p2190
Refer to: p2184, p2190
Refer to: A07926
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2190 < p2189
Refer to: p2184, p2189
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
p2187[0...n] Load monitoring torque threshold 2 upper / M_thresh 2 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2188[0...n] Load monitoring torque threshold 2 lower / M_thresh 2 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2189[0...n] Load monitoring torque threshold 3 upper / M_thresh 3 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2190[0...n] Load monitoring torque threshold 3 lower / M_thresh 3 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]