2 Parameters
2.2 List of parameters
SINAMICS G120D
148 List Manual (LH14), 01/2016, A5E33842313
Description: Displays the PROFIdrive profile number and profile version.
Constant value = 0329 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 29 hex = Version 4.1
Note: When the parameter is read via PROFIdrive, the Octet String 2 data type applies.
Description: Displays the system runtime in ms since the last POWER ON.
Note: The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
Description: The parameter is used to initiate the reset of the drive parameters.
Parameters p0100, p0205 are not reset.
The following motor parameters are defined in accordance with the power unit: p0300 ... p0311.
When downloading settings 10, 11, 12, the buffer memory mode is automatically de-activated (p0014 = 0).
Value: 0: Inactive
1: Start a parameter reset
3: Start download of volatile parameters from RAM
5: Starts a safety parameter reset
10: Start loading the parameters saved with p0971=10
11: Start loading the parameters saved with p0971=11
12: Start loading the parameters saved with p0971=12
30: Start loading the delivery state saved with p0971=30
100: Start a BICO interconnection reset
300: Only Siemens int
Dependency: Refer to: F01659
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When the buffer memory is active (see p0014), the actual parameters are backed up from RAM to ROM when a
parameter set is loaded (p0970 = 10, 11, 12).
Peculiarities of communication via PROFIBUS DP:
- Communication with Class 1 masters (e.g. S7 controllers) is interrupted.
- Communication with Class 2 masters (e.g. STARTER) is retained.
r0965 PROFIdrive profile number / PD profile number
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p0969 System runtime relative / t_System relative
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8050, 8060
Min Max Factory setting
0 [ms] 4294967295 [ms] 0 [ms]
p0970 Reset drive parameters / Drive par reset
Access level: 1 Calculated: - Data type: Unsigned16
Can be changed: C(1, 30) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 300 0