EasyManua.ls Logo

Siemens SINAMICS G120D CU240D-2 DP - p0436[0...n] Encoder SSI parity bit; Enc SSI parity bit; p0437[0...n] Sensor Module configuration extended; SM config ext

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G120D
86 List Manual (LH14), 01/2016, A5E33842313
Example:
p0435 = 1014
--> The evaluation is switched in and the alarm bit is at position 14 with a low level.
p0435 = 1114
--> The evaluation is switched in and the alarm bit is at position 14 with a high level.
Description: Sets the position and parity of the parity bit in the SSI protocol.
Notice: The bit may only be positioned before (p0446) or after (p0448) the absolute value in the SSI protocol.
Note: Value = dcba
ba: Position of the parity bit in the protocol (0 ... 63).
c: Parity (0: even, 1: uneven).
d: State of the evaluation (0: Off, 1: On).
Example:
p0436 = 1015
--> The evaluation is switched in and the parity bit is at position 15 with even parity.
p0436 = 1115
--> The evaluation is switched in and the parity bit is at position 15 with uneven parity.
Description: Sets the extended configuration of the Sensor Module.
Dependency: Refer to: p0430, r0459
Note: A value of zero is displayed if an encoder is not present.
For bit 00:
When the data logger (trace) is activated, in the case of a fault, data before and after the event are recorded (traced)
and saved in files on the non-volatile memory medium. Experts can then evaluate this data.
For bit 01:
If bit = 0, the zero mark is evaluated by ANDing tracks A and B and the zero mark.
For bit = 1, the zero mark is evaluated depending on the direction of rotation detected. For a positive direction of
rotation, the positive edge of the zero mark is considered and for a negative direction of rotation, the negative edge of
the zero mark.
p0436[0...n] Encoder SSI parity bit / Enc SSI parity bit
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 0
p0437[0...n] Sensor Module configuration extended / SM config ext
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0000 0000 0000 1000 0000
0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Data logger Yes No -
01 Zero mark edge detection Yes No -
02 Correction position actual value XIST1 Yes No -
04 Edge evaluation bit 0 Yes No -
05 Edge evaluation bit 1 Yes No -
06 Freeze the speed actual value for dn/dt
errors
Yes No -
11 Fault handling after PROFIdrive Yes No -
12 Activate additional messages Yes No -
13 Support absolute position for incremental
encoder
Yes No 4750
26 Deselect track monitoring Yes No -

Table of Contents