2 Parameters
2.2 List of parameters
SINAMICS G120D
436 List Manual (LH14), 01/2016, A5E33842313
For bit 00:
For bit = 1 and with the SSM safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the feedback signal has a 0 signal level.
For bit = 0 and with the SSM safety function activated, the following applies:
- Monitoring continues during pulse suppression. The feedback signal last displayed before pulse suppression is kept
and the system goes into the STO state.
For bit 08:
For bit = 1 and with the SDI safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the status signal indicates inactive.
For bit = 0 and with the SDI safety function activated, the following applies:
- Monitoring continues during pulse suppression. The status signal indicates active and the system goes into the STO
state.
Description: Sets the denominator for the gearbox between the motor and the load.
Index: [0] = Gearbox 1
[1] = Gearbox 2
[2] = Gearbox 3
[3] = Gearbox 4
[4] = Gearbox 5
[5] = Gearbox 6
[6] = Gearbox 7
[7] = Gearbox 8
Dependency: Refer to: p9322
Notice: It is not possible to change over the gearbox stages. Gearbox 1 (index 0) is always active.
Description: Sets the numerator for the gearbox between the motor and the load.
Index: [0] = Gearbox 1
[1] = Gearbox 2
[2] = Gearbox 3
[3] = Gearbox 4
[4] = Gearbox 5
[5] = Gearbox 6
[6] = Gearbox 7
[7] = Gearbox 8
Dependency: Refer to: p9321
Notice: It is not possible to change over the gearbox stages. Gearbox 1 (index 0) is always active.
Note: In the case of encoderless monitoring functions, the pole pair number must be multiplied by the numerator of the
gearbox ratio.
Example:
Gearbox ratio 1:4, pole pair number (r0313) = 2
--> p9321 = 1, p9322 = 8 (4 x 2)
p9321[0...7] SI Motion gearbox motor/load denominator (processor 2) / SI Mtn gear den P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 2147000000 1
p9322[0...7] SI Motion gearbox motor/load numerator (processor 2) / SI Mtn gear num P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 2147000000 1