2 Parameters
2.2 List of parameters
SINAMICS G120D
64 List Manual (LH14), 01/2016, A5E33842313
Description: Sets the maximum motor speed.
Dependency: Refer to: p1082
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0322 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly.
Note: The parameter has no significance for a value of p0322 = 0.
Description: Sets the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0323 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly.
Note: The parameter has no effect for induction motors.
The parameter has not effect for synchronous motors if a value of 0.0 is entered. The user-selectable current limit is
entered into p0640.
Description: Sets the current for the 1st phase of the two-stage technique for pole position identification routine.
The current of the 2nd phase is set in p0329.
The two-stage technique is selected with p1980 = 4.
Dependency: Refer to: p0329, p1980, r1984, r1985, r1987
Refer to: F07969
Notice: When the motor code (p0301) is changed, it is possible that p0325 is not pre-assigned.
p0325 can be pre-assigned using p0340 = 3.
Note: The value is automatically pre-assigned for the following events:
- For p0325 = 0 and automatic calculation of the closed-loop control parameters (p0340 = 1, 2, 3).
- for quick commissioning (p3900 = 1, 2, 3).
Description: Sets the correction factor for the stall torque/force at a 600 V DC link voltage.
p0322[0...n] Maximum motor speed / Mot n_max
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [rpm] 210000.0 [rpm] 0.0 [rpm]
p0323[0...n] Maximum motor current / Mot I_max
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [Arms] 20000.00 [Arms] 0.00 [Arms]
p0325[0...n] Motor pole position identification current 1st phase / Mot PolID I 1st ph
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [Arms] 10000.000 [Arms] 0.000 [Arms]
p0326[0...n] Motor stall torque correction factor / Mot M_stall_corr
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
5 [%] 300 [%] 100 [%]