EasyManua.ls Logo

Siemens SINAMICS G120D CU240D-2 DP - p1501[0...n] BI: Change over between closed-loop speed;torque control; Changeov n;M_ctrl; p1502[0...n] BI: Freeze moment of inertia estimator; J_estim freeze; p1503[0...n] CI: Torque setpoint; M_set

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
219
2 Parameters
2.2 List of parameters
Description: Sets the signal source for toggling between speed and torque control.
0 signal: Closed-loop speed control
1 signal: Closed-loop torque control
Dependency: The input connectors to enter the torque are provided using p1511, p1512 and p1513.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1300
Notice: If the closed-loop torque control is not activated (p1300) and a change is made to closed-loop torque control (p1501),
OFF1 (p0840) does not have its own braking response but pulse suppression when standstill is detected (p1226,
p1227).
Note: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to freeze the estimated moment of inertia.
0 signal:
Moment of inertia estimator active
1 signal:
Determined moment of inertia frozen.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1300
Note: Only active when the "moment of inertia estimator" function module is active (r0108.10 = 1) and p1400.18 =1.
For operation with encoder, p1400.23 must also be set to 1.
Description: Sets the signal source for the torque setpoint for torque control.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note: A change is made to closed-loop torque control if, in p1300, closed-loop torque control was selected or if the
selection was made using the changeover source in p1501.
it is also possible to change over in operation using p1501.
p1501[0...n] BI: Change over between closed-loop speed/torque control / Changeov n/M_ctrl
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2520, 6020
Min Max Factory setting
- - 0
p1502[0...n] BI: Freeze moment of inertia estimator / J_estim freeze
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
p1503[0...n] CI: Torque setpoint / M_set
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 6020, 6060
Min Max Factory setting
- - 0

Table of Contents

Related product manuals