Siemens SINAMICS G120D CU240D-2 DP - p1312[0...n] Starting current (voltage boost) when starting; I_start start; r1315 Voltage boost total; U_boost total; p1320[0...n] U;f control programmable characteristic frequency 1; Uf char f1; p1321[0...n] U;f control programmable characteristic voltage 1; Uf char U1

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
197
2 Parameters
2.2 List of parameters
Description: Setting for an additional voltage boost when powering-up, however, only for the first acceleration phase.
The voltage boost becomes effective for a positive setpoint increase and disappears as soon as the setpoint has
been reached. The build-up and withdrawal of the voltage boost are smoothed.
Dependency: The current limit p0640 limits the boost.
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1300, p1310, p1311, r1315
Notice: The voltage boost results in a higher motor temperature increase.
Note: The voltage boost when accelerating can improve the response to small, positive setpoint changes.
Assigning priorities for the voltage boosts: refer to p1310
Description: Displays the total resulting voltage boost in volt.
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1310, p1311, p1312
Description: The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
Dependency: Selects the freely programmable characteristic using p1300 = 3.
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard
characteristic is used that contains the rated motor operating point.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1300, p1310, p1311, p1321, p1322, p1323, p1324, p1325, p1326, p1327
Note: Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
Description: The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
p1312[0...n] Starting current (voltage boost) when starting / I_start start
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6300, 6301
Min Max Factory setting
0.0 [%] 250.0 [%] 0.0 [%]
r1315 Voltage boost total / U_boost total
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6301
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p1320[0...n] U/f control programmable characteristic frequency 1 / Uf char f1
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6301
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]
p1321[0...n] U/f control programmable characteristic voltage 1 / Uf char U1
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6301
Min Max Factory setting
0.0 [Vrms] 10000.0 [Vrms] 0.0 [Vrms]